23. FIRE FIGHTING WATER TANKERS.
A. OBSERVATION: MORE EFFECTIVE QUANTITIES AND PLANNING FOR
ADDITIONAL WATER FOR FIRE FIGHTING ARE NEEDED TO BECOME PART OF
THE INVENTORY PACKAGE FOR FIELD HOSPITALS.
B. DISCUSSION: THE INITIAL INVENTORY AND PLANNING FOR THE
ADDITIONAL WATER SOURCES FOR FIRE FIGHTING INCLUDED TANKERS AND
DRAFTING SUCTION HOSES 50' RECEIVED FOR PUMPER.
C. LESSONS LEARNED: ADDITIONAL WATER. ADDITIONAL WATER
SOURCES HAVE BEEN IDENTIFIED FROM FOUR SOURCES;
(1) WATER TANKERS AT PWD - NEED BOTTOM SIDE MANIFOLDS FOR 4
1/2 CONNECTION AS DESCRIBED.
(2) DRAFTING FROM SALT WATER - DRAFTING FROM SALT WATER WITH
EN31NE NUMBER I WAS FOUND NOT TO WORK AS THE LIFT WAS TOO GREAT
OFF THE SEA WALL. HOWEVER ONE OR TWO P250 PUMPS COULD BE STAGED
ALONG THE SEA WALL AT THE HELD PAD FOR ADDITIONAL WATER. (IT
COULD ALSO BE ATTACHED TO A PERMANENTLY STAGED WATER TANKER.)
WITH A AKRON IN LINE FOAM EDUCTOR, A FOAM DELIVERY STATION COULD
ALSO BE PLACED THERE.
(3) UNDERGROUND 10" SALT WATER MAIN: THE UNDERGROUND WALT
WATER SYSTEM IS NOT NORMALLY KEPT PRESSURIZED BUT TAKES ABOUT 15
MINUTES FOR THE PRESSURE TO BUILD UP AFTER THE SALT WATER PUMP IS
TURNED ON. HEAVY COVER PLATES ARE LIFTED BY A SPECIAL LIFTING
TOOL TO GAIN ACCESS. ONE 2 1/2" OUTLET IS TURNED ON BY A SQUARE
KEY WRENCH AND CAN PRODUCE ABOUT 500 GPM. THE LIFTERS WRENCH,
AND STANDPIPE ARE CURRENTLY BEING MANUFACTURED.
(4) TANKERS FROM PORT AL JUSAIL FIRE DEPT: FLEET HOSPITAL
FIVE HAS AN AGREEMENT FOR PORT FIRE DEPT TO RESPOND IN EVENT OF
FIRE.
0. RECOMMENDED ACTIONS:
S COME FACT DRY EQUIPPED WITH 4 1/2" AND P250
MANIFOLD CONNECTIONS.
(2) P250 PUMP AND AKRON FOAM EDUCTOR TO BECOME PART OF
INVENTORY.
(3) LIFTER, SQUARE KEY WRENCH, AND STANDPIPE ARE BEING
MANUFACTURED.
(4) CONTINUE FIRE DRILLS TO IMPROVE RESPONSE TIME.
E. COMMENTS: NONE
24. FIREFIGHTING COMMUNICATIONS.
A. OBSERVATION: MORE EFFECTIVE AND SUITABLE
COMMUNICATIONS, CONTROL AND ORGANIZATION FOR THE FIRE DEPARTMENT
ARE NEEDED TO BECOME PART OF THE INVENTORY "PACKAGE" FOR A FIELD
HOSPITAL.
B. DISCUSSION: THE INITIAL INVENTORY AND PLANNING FOR
COMMUNICATIONS, CONTROL AND ORGANIZATION INCLUDED:
(1) RADIOS, I PRC, 2 HAND HELD UNITS.
(2) NO AIR CONTROL PLANNED FOR AT HELD LANDING AREA.
C. LESSONS LEARNED:. COMMUNICATIONS, CONTROL AND
ORGANIZATION:
(1) THE MAIN PROBLEM IN THIS CATEGORY IS THAT A VISUAL
CONTROL TOWER IS NEEDED AT THE HELD PORT TO BE MANNED BY AIR
CONTROL MAN OR COMPETENT RADIOMAN. NUMEROUS HELOS ARRIVING AND
DEPARTING CREATES A DANGEROUS SITUATION.
UNCLASSIFIED
Document Page: First | Prev | Next | All | Image | This Release | Search
Document 20 f:/Week-36/BX300052/FLEET HOSPITAL WORKING PAPERS VARIOUS SOURCES CNA 2837/navgram lessons learned f h f 1 jan 91 to 31 jan:1018961451347
Control Fields 17
File Room = sep96_declassified
File Cabinet = Week-36
Box ID = BX300052
Unit = FLEET HOSP
Parent Organization = NAVCENTCOM
Folder Title = FLEET HOSPITAL WORKING PAPERS VARIOUS SOURCES CNA 2837
Folder Seq # = 11
Subject = NAVGRAM LESSONS LEARNED F H F 1 JAN 91 TO 31 JAN
Document Seq # = 58
Document Date =
Scan Date =
Queued for Declassification = 01-JAN-1980
Short Term Referral = 01-JAN-1980
Long Term Referral = 01-JAN-1980
Permanent Referral = 01-JAN-1980
Non-Health Related Document = 01-JAN-1980
Declassified = 18-OCT-1996