                                      ERLECTRICALI

          15. PROBLEM: INSUFFICIENT GROUND ROD CLAMPS PROVIDED.

              SOLUTION: PROVIDE GROUND ROD CLAMPS IN ONE LOCATION WITH THE
          GROUND RODS FOR USE WHERE NECESSARY.

          16. PROBLEM: LIGHT BULB WATTAGE [IOOWATTS3 FOR GENERAL PURPOSE
          TENTS TOO GREAT.


              SOLUTION: REDUCE TO 4OW AND OOW.

          17. PROBLEM: TILT-TOP FRYERS IN GALLEY PULL 56AMPS BUT ARE SHOWN
          ON THE DRAVVINGS TO BE TIED INTO A 20AMP BREAKER IN A 'C' PANEL.

              SOLUTION: REDESIGN TO SHOW TIE-IN TO A 'B' PANEL.